    The digital ground resistance tester has sound and light alarm, data storage and data retention functions, and the measurement range is 0.01Ω-200Ω. The clamp-type ground resistance tester is widely used in ground resistance measurement and loop resistance measurement of power, telecommunications, meteorology, oil fields, construction and industrial electrical equipment.
    SKU: T-ERT-2000
    $400.74
    i h
    Free shipping
    Delivery date: 6-12 days
    Overview

    The clamp-type earth resistance tester can accurately test the ground resistance with a measurement range of 0.01Ω to 200Ω. The digital ground tester is suitable for grounding system measurement in power systems, telecommunications, meteorology, oil fields and buildings.

    Details

    Details of digital earth resistance testers

    The digital earth resistance tester is equipped with 32mm jaws, with a measurement range of 0.010 Ω~200 Ω.

    • This reliable resistance tester is a high-quality grounding resistance tester.
    • The clamp-type grounding insulation tester has a clamp opening size of 32mm, and its sturdy design makes it a high-performance electrical instrument.
    • The grounding resistance test is a non-contact measurement, which is safe and fast.
    • When measuring the loop grounding system, there is no need to disconnect the grounding lead and auxiliary grounding electrode, saving time and achieving better results.
    • The clamp-type earth resistance tester can measure grounding faults that cannot be measured by traditional methods and is suitable for situations where traditional methods cannot be used.
    • It has functions such as sound and light alarm, data storage, and data retention.
    • LCD high-definition display of measurement data, data can be backlit for display.

    Specifications

    Model T-ERT-2000A+
    Resistance Range 0.010Ω~200Ω
    Current Range -
    Clamp Size 65mm×32mm
    Tester Size 285mm×85mm×56mm 
    Resistance Tester Weight 2.3kg (including accessories)
    Power Supply 6V DC ( 4 PCS of No.5 Alkaline dry batteries)
    Single Measurement Time 0.5 second
    LCD Screen 4 Digits LCD display,  47mm×28.5mm
    Data Memory 99 groups
    Audible And Visible Alarm "du—du—du" for alarming, press AL to turn on/off
    Alarm Threshold Setting Range Resistance: 1-199Ω
    Jaw Opening Size 32mm
    Protection Class Double insulation
    Shift Automatically
    Accessories Resistance Tester: 1PCS; Test Ring: 1PCS; Instrument Case: 1PCS
    Clamp Meter Weight About 1100g (including battery)

    Resistance Measurement Accuracy

    Range Resolution Accuracy
    0.010Ω-0.099Ω 0.001Ω ±(1%rdg+0.01Ω)
    0.10Ω-0.99Ω 0.01Ω ±(1%rdg+0.01Ω)
    1.0Ω-49.9Ω 0.1Ω ±(1%rdg+0.1)
    50.0Ω-99.5Ω 0.5Ω ±(1.5%rdg+0.5)
    100Ω-200Ω ±(2%rdg+1Ω)

    Applications

    The measuring range of the tool earth resistance tester is 0.010Ω~200Ω. The clamp ground resistance tester is widely used in ground resistance measurement and loop resistance measurement in the fields of power, telecommunications, meteorology, oil fields, construction and industrial electrical equipment.
    When using the loop to measure the grounding system, there is no need to disconnect the ground wire without an auxiliary electrode, which means safer and faster.

    Applications of earth resistance tester

    Tips: Why do you need to test the ground resistance?

    Use a digital ground resistance tester to measure the ground resistance. We can judge whether the ground resistance is within a reasonable range based on this value, so as to achieve the effect of protecting the grounding device. If the ground resistance is required when installing electrical equipment, it can prevent electric shock. Since some electrical housings are made of metal, they will inevitably be damaged after long-term use, resulting in the destruction of the insulator.
    In order to avoid electric shock accidents, a ground resistance tester is needed.

    0.0 0
    Write your own review Close
    *
    *